kW to Amps: The Quick Answer
To convert kilowatts to amps, multiply kilowatts by 1000 to get watts, then divide by the circuit voltage. For single-phase AC, also divide by the power factor; for three-phase AC, divide by 1.732 × voltage × power factor; for DC, just divide watts by volts. For example, a 3.7 kW appliance on a 230 V single-phase circuit with 0.85 power factor draws about 18.9 amps.
The Three Formulas
Every kW-to-amps conversion uses one of three formulas, depending on the circuit type. P is power in kilowatts, V is voltage in volts, and PF is power factor (1 for DC and resistive loads, typically 0.8–0.95 for motors).
- DC: I = (P × 1000) ÷ V
- Single-phase AC: I = (P × 1000) ÷ (V × PF)
- Three-phase AC: I = (P × 1000) ÷ (√3 × V × PF)
Worked Examples
Example 1 — Workshop heater: A 3.7 kW heater on 230 V single-phase, PF 0.85. I = 3700 ÷ (230 × 0.85) = 3700 ÷ 195.5 = 18.9 A. A 20 A breaker with 4 mm² wire is the standard choice.
Example 2 — Industrial pump: A 7.5 kW pump on 415 V three-phase, PF 0.8. I = 7500 ÷ (1.732 × 415 × 0.8) = 7500 ÷ 575 = 13.0 A. This fits comfortably on a 16 A three-phase breaker.
Example 3 — DC solar array: A 5 kW array charging a 48 V battery bank. I = 5000 ÷ 48 = 104.2 A. This is why solar charge controllers for 48 V systems are rated at 100+ amps, and why cable thickness matters so much at low voltage.
Reading a Motor Nameplate
Motor nameplates list rated power in kW, voltage, and sometimes full-load current directly. When only kW is given, use the three-phase formula with the motor’s rated power factor (usually printed as “cos φ” on the plate, commonly 0.8–0.87). Example: a 2.2 kW motor nameplated 400 V, cos φ 0.83: I = 2200 ÷ (1.732 × 400 × 0.83) = 2200 ÷ 575 = 3.8 A full-load current. Size the overload relay at 105–115% of this value, and the breaker per your local code’s motor rules (often 250% of FLA for instantaneous trip).
Sizing Your Breaker From kW
Once you know the current, breaker sizing follows a simple workflow: 1) calculate full-load amps, 2) multiply by 1.25 for continuous loads (running 3+ hours, per NEC 210.19), 3) pick the next standard breaker size up. Example: a 9.6 kW continuous load at 240 V single-phase, PF 1: I = 9600 ÷ 240 = 40 A; 40 × 1.25 = 50 A → use a 50 A breaker. Undersizing breakers is the most common DIY mistake — the breaker must protect the wire, and the wire must carry the load.
Solar and Battery Sizing
Off-grid designers live in amps, not kilowatts. Convert each load to amps at the battery voltage (12, 24, or 48 V), not the appliance voltage, because an inverter draws from the battery bank. Example: running a 1.5 kW air conditioner through an inverter on a 24 V bank: I = 1500 ÷ 24 = 62.5 A from the batteries (before inverter losses of ~10–15%). This single calculation determines battery cable size, fuse rating, and how fast your bank drains.
Mistakes That Trip Breakers
- Forgetting power factor: using PF 1 for a motor load underestimates current by 15–25%.
- Mixing line and phase voltage: on three-phase, always use line-to-line voltage (e.g., 415 V, not 240 V) with the √3 formula.
- Ignoring continuous-load derating: a breaker carrying its full rating for hours will eventually trip on thermal buildup — hence the 125% rule.
- Using kW where kVA is needed: generator and transformer ratings are in kVA (apparent power); converting with kW alone undersizes them.